Телефон: | +7 (495) 517-13-99 |
Факс: | +7 (495) 661-66-75 |
E-mail: | sale@prom-bez.ru |
alabai.rus | |
Быстрая навигация: Каталог продукции Энергетические кабели - Испытания и диагностика Испытание напряжением СНЧ (VLF) VLF (СНЧ) 28
Серия: SebaKMT
запросить ценуПожалуйста укажите свои данные и мы оперативно свяжемся с вами и уточним цену на интересующий вас товар:
Function description:
In accordance with most regulations, cables and joints must be tested after installation or repair. For this test the breakdown strength of the cable is tested.
The portable VLF Test System CR 28 kV of Seba KMT can be used to test the cables in conjunction with the according local regulations for operating voltage levels up to 15 kV for new cables and 22 kV for aged cables at 4,6 ?F cable capacity.
By using the patented Seba KMT 0.1 Hz Cosine Square Wave Voltage, weak and for further operation critical spots in PE, XLPE but also in paper cables are brought to a controlled breakdown very fast without causing additional damage or ageing to the cable insulation.
The VLF Test System CR 28 kV consists of a DC source, which charges the test object up to the required test voltage level and the commutator unit (switched rectifier) which performs the regular 5 second interval polarity change.
The change over from one polarity to the reverse one is performed wit the support of the switched rectifier, an inductivity (choke) and a capacitor, which is build of the internal 0.3 ?F and the cable capacity itself. The L / C resonance circuit produces a cosine shaped voltage with slopes identical to a 50 Hz sine wave.
Technical Features
Optional equipment
Output voltage source | 12 mA |
Display range leakage current measurement | 0 … 12 mA |
Display resolution | 10 ?A |
Output voltage VLF | 0 - 28 kVeff |
Voltage shape | Cosine Square Wave |
Change over slope | approx. 5 ms analogue to 50 Hz mains |
Frequency | 0.1 Hz |
Output voltage DC | 0 ... 28 kV |
Testable cable capacity | max. 4,6 ?F |
Sheath fault location voltage | 0 – 10 kV |
Pulse rate for sheath fault location | 4s 1:3 4s 1:5 6s 1:5 6s 1:9 |
Discharge unit | integrated, 4,6 ?F in 5 s |
Power supply | 230 V, 50 Hz, approx. 2.5 A 120 V, 60 Hz, approx. 5 A |
Operating temperature | -20°C ... 50°C |
Weight | approx. 25 kg control module approx. 25 kg power module |
Dimensions (W x H x D) | 550 x 700 x 420 mm |
Посмотреть другие товары из раздела "Испытание напряжением СНЧ (VLF)"